Show simple item record

AuthorMoshfeghian, Mahmood Moshfeghian, Mahmood
Available date2009-11-25T13:02:59Z
Publication Date1992
Publication NameEngineering Journal of Qatar University
CitationEngineering Journal of Qatar University, 1992, Vol. 5, Pages 35-55.
URIhttp://hdl.handle.net/10576/7813
AbstractThe ability of three equations of state (EOS) for calculating the thermodynamic properties of refrigerants has been studied for 35 pure component refrigerants. Three equations of state studied were the Soave-Redlich-Kwong (SRK), Peng-Robinson (PR) and Parameters From Group Contribution (PFGC). For each refrigerant, the vapor pressure, saturated vapor volume, saturated liquid density, and heat of vaporization were calculated and compared with the values reported in the ASHRAE hand-book. For each refrigerant a range of temperature from about the triple point to the critical point was covered. Specific EOS parameters such as acentric factor (for SRK and PR), b. s, E"" E"', E12' (for PFGC) were optimized to achieve better agreement between calculated values and the ASHRAE data. The optimized acentric factors and PFGC parameters for several compounds are presented. Sample graphical error analyses are shown.
Languageen
PublisherQatar University
SubjectEngineering: Research Teaching
TitlePrediction Of Refrigerant Thermodynamic Properties By Equations Of State
TypeArticle
Pagination35-55
Volume Number5


Files in this item

Thumbnail

This item appears in the following Collection(s)

Show simple item record