Show simple item record

AuthorBesharatifard, Hamidreza
AuthorHasanzadeh, Saeed
AuthorHeydarian-Forushani, Ehsan
AuthorMuyeen, S. M.
Available date2023-02-27T11:01:50Z
Publication Date2022-01-01
Publication NameIEEE Access
Identifierhttp://dx.doi.org/10.1109/ACCESS.2022.3177603
CitationBesharatifard, H., Hasanzadeh, S., Heydarian-Forushani, E., & Muyeen, S. M. (2022). Acoustic based localization of partial discharge inside oil-filled transformers. IEEE Access, 10, 55288-55297.‏
URIhttps://www.scopus.com/inward/record.uri?partnerID=HzOxMe3b&scp=85130821431&origin=inward
URIhttp://hdl.handle.net/10576/40473
AbstractThis paper addresses the localization of Partial Discharge through a 3D Finite Element Method analysis of acoustic wave propagation inside a 3-phase 35kV transformer with the help of COMSOL Multiphysics software. Due to the complexity inside transformers, acoustic waves generated by PDs cannot simply be detected with typical acoustic sensors, especially when PDs happen inside inner windings. These waves are distorted and attenuated along with their propagation. The type, number, and position of sensors are essential factors in PD localization inside a transformer. A new installation arrangement of fiber-optic acoustic sensors inside the transformers is proposed with this information. This array of acoustic sensors has significant effects on PD localization accuracy and has immunity from on-site noise and interference; more importantly, they can be installed after transformer manufacturing. They are reachable if needed to be repaired or replaced. Several numerical studies have been carried out considering different PD source positions, and the Levenberge-Marquardt algorithm is employed for solving localization equations.
SponsorThis work was supported by Qatar National Library
Languageen
PublisherInstitute of Electrical and Electronics Engineers Inc.
SubjectAcoustic signal propagation analysis
FEM simulation
Levenberg-Marquardt algorithm
Partial discharge localization
Power transformers
TitleAcoustic Based Localization of Partial Discharge Inside Oil-Filled Transformers
TypeArticle
Pagination55288-55297