Improving the performance of a commercial absorption cooling system by using ejector: A theoretical study
Author | Mukhtar, Hamza K. |
Author | Ghani, Saud |
Available date | 2024-11-18T04:33:19Z |
Publication Date | 2023 |
Publication Name | Case Studies in Thermal Engineering |
Resource | Scopus |
Identifier | http://dx.doi.org/10.1016/j.csite.2023.102967 |
ISSN | 2214157X |
Abstract | Absorption cooling systems (ACS) have lower coefficients of performance (COP) compared to direct expansion (DX) cooling systems. Nevertheless, ACS offers a green alternative to typical DX systems. In this study, a numerical model was developed for the commercial low-capacity Robur absorption cooling system (RACS). The model was developed based on mass, concentration, and energy balance equations, in addition to heat transfer equations. The model results were validated against experimental data available in the literature for the same cooling unit yielding a good agreement. Hence, to improve the COP of the RACS, a vapor ejector was introduced between the generator and the condenser. An improvement of 70.6% in the COP was obtained at the design condition. A parametric analysis was implemented to study the significance of the key parameters in the RACS performance. It was found that the increase in the ambient temperature not only increased the activation temperature, but it also decreased the COP and increased the circulation ratio (CR). Consequently, in hot environments, lowering the evaporator temperature is recommended to avoid the need for higher CR. Optimizing the nozzle throat and the mixing tube diameter improves the ejector performance, and hence the RACS performance, as long as the ejector operates under critical conditions. Finally, the absorber coil was found to have the most significance on the RACS performance in comparison with the rectifier coil and the refrigerant heat exchanger. |
Sponsor | The work in this paper was funded by Qatar National Research Fund under its National Priorities Research Program [Award number NPRP11S-0114-180295 ]. The contents of this work are solely the responsibility of the authors and do not necessarily represent the official views of the Qatar National Research Fund. Open Access funding was supported by the Qatar National Library . |
Language | en |
Publisher | Elsevier |
Subject | Absorption cooling Ammonia-water Cooling system Ejector Robur chiller |
Type | Article |
Volume Number | 45 |
Check access options
Files in this item
This item appears in the following Collection(s)
-
Mechanical & Industrial Engineering [1396 items ]