Show simple item record

AuthorShiquan, Wang
AuthorWei, Wenzhe
AuthorLuo, Jianfei
AuthorWang, Wei
AuthorSun, Yuying
AuthorLi, Zhaoyang
AuthorHuang, Chengyang
AuthorTang, Rui
AuthorDeng, Shiming
Available date2025-07-01T07:59:48Z
Publication Date2025-01-01
Publication NameEnergy and Buildings
Identifierhttp://dx.doi.org/10.1016/j.enbuild.2024.115079
CitationWang, S., Wei, W., Luo, J., Wang, W., Sun, Y., Li, Z., ... & Deng, S. (2025). A prediction model of the optimal defrosting initiating time for the air source heat pumps with different configurations and operations. Energy and Buildings, 326, 115079.
ISSN03787788
URIhttps://www.sciencedirect.com/science/article/pii/S0378778824011952
URIhttp://hdl.handle.net/10576/65929
AbstractFrosting is a critical challenge that affects the energy efficiency of air source heat pumps (ASHPs). Defrosting periodically is the most widely used method to solve this problem. However, the rate of frosting varies considerably for ASHPs due to their configurations and operations (CICO) being different. This leads to the obvious differences in their defrosting initiating time. Defrosting too early or too late will both cause energy loss. To ensure the efficient operation of ASHPs, the variations of energy loss coefficient caused by frosting-defrosting (εNL) and the defrosting initiating time for ASHPs with different CICO values were investigated. Based on the theory of optimal defrosting initiating time (Topt) and experimental results under different frosting durations, the Topt for different ASHPs is found. Then, a prediction model for ASHPs with different CICO values is established. Results show that there is a Topt for ASHPs with different CICO values, respectively. Under the frosting condition of 2/1 ℃, the Topt increases with the rise of CICO values. When the CICO values increase from 3.14 to 22.44, the corresponding Topt increases from 22 min to 148 min. By fitting the Topt and CICO values, a cubic mathematical model for the prediction of the optimal defrosting time of ASHPs has been developed.
SponsorThis work was supported by the General Program of the National Natural Science Foundation of China (Grant No. 52378086).
Languageen
PublisherElsevier
SubjectAir source heat pumps
Optimal defrosting initiating time
Different configurations and operations
Frosting energy loss
Defrosting energy loss
TitleA prediction model of the optimal defrosting initiating time for the air source heat pumps with different configurations and operations