Show simple item record

AuthorSoliman, S.A.
AuthorAlammari, R.A.
AuthorMostafa, M.A.
Available date2024-05-23T05:12:37Z
Publication Date2004
Publication Name2004 Large Engineering Systems Conference on Power Engineering - Conference Proceedings; Theme: Energy for the Day After Tomorrow
ResourceScopus
Identifierhttp://dx.doi.org/10.1109/LESCPE.2004.1356295
URIhttp://hdl.handle.net/10576/55319
AbstractThe conventional method for determining the parameters of the transformer is to performing the open and short-circuited tests. The method is only suitable for off-line application. This paper presents an alternative approach to conventional open and short-circuit test for determining the parameters of N-windings transformer operating at power frequency on an on-line mode. This approach is based on linear least errors square (LES) algorithm and uses the digitized samples of the input current and voltage as well as the output current and voltage of the transformer windings. The proposed algorithm estimates the winding parameters in two steps; while in the first step the algorithm identifying the winding parameters, in the second step, the algorithm identifying the core parameters. The proposed algorithm is applied to a two-windings transformer and simulated results are reported in this paper.
Languageen
PublisherIEEE
SubjectLinear least errors square
Parameters identification
Power transformer model
TitleOn-line estimation of transformer model parameters
TypeConference
Pagination170-178
dc.accessType Abstract Only


Files in this item

FilesSizeFormatView

There are no files associated with this item.

This item appears in the following Collection(s)