Show simple item record

AuthorZhaoyang, Li
AuthorWei, Wenzhe
AuthorWang, Wei
AuthorSun, Yuying
AuthorWang, Shiquan
AuthorLin, Yao
AuthorHuang, Chengyang
AuthorDeng, Shiming
Available date2025-07-01T07:54:11Z
Publication Date2024-02-01
Publication NameApplied Thermal Engineering
Identifierhttp://dx.doi.org/10.1016/j.applthermaleng.2023.122136
CitationLi, Z., Wei, W., Wang, W., Sun, Y., Wang, S., Lin, Y., ... & Deng, S. (2024). Experimental study on the effects of melted frost icing on the operating performances of air source heat pump. Applied Thermal Engineering, 238, 122136.
ISSN13594311
URIhttps://www.sciencedirect.com/science/article/pii/S1359431123021658
URIhttp://hdl.handle.net/10576/65927
AbstractDefrosting operation is always used to solve its frosting problem at a high humidity environment for air source heat pump units (ASHPs), and at the end of defrosting operation, the residual melted frost may exist on the surface of outdoor coil and freeze into ice in sequent frosting. However, till now, as the residual melted frost icing environment is difficult to create, its quantitative influences on the heating performance of ASHPs is still unknown, especially at different icing levels. To resolve this issue, a control strategy was firstly proposed to make it possible for the residual melted frost to ice. Then, based on the control strategy, the effect of five different icing levels on operating performances of an ASHP unit were investigated. Results indicated that ice can promote the frost formation, and the operating performances of ASHP unit were significantly affected by different icing levels. When the percentage of iced outdoor coil surface was increased from 0% to 15% and 35%, the output heating capacity of ASHP unit was decreased by 11.2% and 23.8%, and meanwhile the COP of ASHP unit was decreased by 7.7% and 16.1%, respectively. The results can assist with the defrosting control optimization of practical products.
SponsorThis work was financially supported by the National Natural Science Foundation of China (No. 52378086) and Carbon Neutral Foundation of Beijing University of Technology.
Languageen
PublisherElsevier
SubjectAir source heat pump
Frosting
Melted frost icing
Defrosting termination temperature
Water retention
TitleExperimental study on the effects of melted frost icing on the operating performances of air source heat pump
TypeArticle
Volume Number238
ESSN1873-5606
dc.accessType Full Text


Files in this item

Thumbnail

This item appears in the following Collection(s)

Show simple item record