الملخصThis paper presents a technique for differential protection of Multi-terminal High Voltage Direct Current (MTHVDC) transmission lines. The proposed technique depends on the electrical current data at both ends of each line section. Discrete Wavelet Transform (DWT) is used to detect DC faults as well as filter out the high frequency transients superimposed on the current signals. An operating signal and a restraining signal are used in this technique to discriminate between internal faults and external faults through their ratio in each section of the MTHVDC. The operating and restraining signals depend on energy contents of the de-noised current signals at both ends of each line section. MTHVDC modeling and relay design are carried out in the MATLAB environment. The results demonstrate the high reliability of the proposed relay in the zonal protection of MTHVDC. All rights reserved.
راعي المشروعThis publication was made possible by NPRP grant NPRP 4-941-2-356 from the Qatar National Research Fund (a member of Qatar Foundation). The statements made herein are solely the responsibility of the authors.
اللغةen
الناشرElsevier Ltd
الموضوعMulti-terminal HVDC
Protection
Wavelet transform
Wind farm
العنوانA differential protection technique for multi-terminal HVDC