Show simple item record

AuthorRahman, Syed
AuthorKhan, Irfan Ahmad
AuthorIqbal, Atif
Available date2023-05-21T08:32:42Z
Publication Date2023
Publication Name2023 IEEE Texas Power and Energy Conference, TPEC 2023
ResourceScopus
URIhttp://dx.doi.org/10.1109/TPEC56611.2023.10078476
URIhttp://hdl.handle.net/10576/43071
AbstractDistributed generators (DGs) have emerged as a go-to solution to accommodate increasing loads, with the existing grid infrastructure. The DG-injected power can be consumed locally, thereby reducing the grid current and improving the voltage profile. The power-electronics interface-based DGs, controlled as current sources, employ a grid-side filter for injecting sinusoidal current into the grid. As the filter is designed to meet IEEE compliance for DG grid integration, the current THD is restricted to less than 5%. Although the compliance is met, these harmonics injected into the grid significantly deteriorate the harmonic profile of the entire grid. This study quantifies the impact of two types of DGs - constant power DGs (Type-1) and varying power DGs (Type-II) on the utility grid. An actual 24-hour data-based IEEE 33-bus distribution network, consisting of both linear and non-linear loads, is used to quantify the DGs' harmonic impact. Post-DGs addition, it is observed that Type-I DGs increase the voltage THD by at least 1% at the farthest nodes, although the pattern remains consistent with that of prior DG addition. However, with Type-II DGs, the profile obtained is further deteriorated and inconsistent and exhibits a strong dependence on the power generation of the DG. 2023 IEEE.
SponsorThis publication was made possible by NPRP grant # NPRP-13S-0108-20008 from the Qatar National Research Fund (a member of Qatar Foundation). The statements made herein are solely the responsibility of the authors. REFERENCES [1] A. Poullikkas, "Sustainable options for electric vehicle technologies," Renew. Sustain. Energy Rev., vol. 41, pp. 1277-1287, 2015. [2] S. Rahman, I. A. Khan, A. A. Khan, A. Mallik, and M. F. Nadeem, "Comprehensive review & impact analysis of integrating projected electric vehicle charging load to the existing low voltage distribution system," Renew. Sustain. Energy Rev., vol. 153, p. 111756, 2022. [3] R. C. Dugan and T. E. Mcdermott, "Distributed generation," IEEE Ind. Appl. Mag., vol. 8, no. 2, pp. 19-25, 2002. [4] A. Ahmed, A. Iqbal, I. Khan, A. Al-Wahedi, H. Mehrjerdi, and S. Rahman, "Impact of EV charging Station Penetration on Harmonic Distortion Level in Utility Distribution Network: A Case Study of Qatar," in 2021 IEEE Texas Power and Energy Conference (TPEC), 2021, pp. 1-6. [5] M. A. Kashem and G. Ledwich, "Multiple distributed generators for distribution feeder voltage support," IEEE Trans. Energy Convers., vol. 20, no. 3, pp. 676-684, 2005. [6] G. B. Gharehpetian and M. Mousavi, Distributed generation systems: design, operation and grid integration. Butterworth-Heinemann, 2017. [7] A. C. Rueda-Medina and A. Padilha-Feltrin, "Distributed generators as providers of reactive power support-A market approach," IEEE Trans. Power Syst., vol. 28, no. 1, pp. 490-502, 2012. [8] DoE-EERE, "Department of Energy - Solar and Wind Grid Services and Reliability Demonstration," 2022, [Online]. Available: https://eere-exchange.energy.gov/. [9] Z. A. Arfeen, A. B. Khairuddin, R. M. Larik, and M. S. Saeed, "Control of distributed generation systems for microgrid applications: A technological review," Int. Trans. Electr. Energy Syst., vol. 29, no. 9, p. e12072, 2019. [10] S. Essallah, A. Khedher, and A. Bouallegue, "Integration of distributed
Languageen
PublisherInstitute of Electrical and Electronics Engineers Inc.
Subjectdecoupled harmonic power flow analysis
distributed generators
IEEE 33-bus system
source harmonics
Total harmonic distortion
TitleImpact of Harmonics of Distributed Generators on the Harmonic Profiling of Distribution Networks