المؤلفPaurobally, Mohammad Roshun
المؤلفSassi, Sadok
المؤلفRenno, Jamil
تاريخ الإتاحة2024-02-29T08:23:37Z
تاريخ النشر2019-01-01
اسم المنشورProceedings of the 26th International Congress on Sound and Vibration, ICSV 2019
الترقيم الدولي الموحد للكتاب 9781999181000
معرّف المصادر الموحدhttps://www.scopus.com/inward/record.uri?partnerID=HzOxMe3b&scp=85084016585&origin=inward
معرّف المصادر الموحدhttp://hdl.handle.net/10576/52481
الملخصVentilation ducts are often lined with passive absorption material for both thermal insulation and noise and vibration reduction. However, the noise reduction performance is not significant at low frequencies. Active Noise Control (ANC) on the other hand can be used in controlling low frequency noise in ducts effectively. This paper presents the main results obtained from the development of an active noise control system for ventilation noise using two approaches. A comparison between the performance of an adaptive feedforward control algorithm and a regenerated reference adaptive algorithm shows that both algorithms provide good noise reduction. Experimental results in the laboratory show that adequate active noise reduction occurs in the frequency range between 100 Hz to 300Hz. The noise attenuation of 20 dB or more for tonal noise can be achieved. The system is also tested in an actual classroom where noise reduction from the ventilation duct is controlled. The results show that the tonal component can be attenuated successfully and a quiet zone achieved in the classroom with a single channel control system
اللغةen
الناشرCanadian Acoustical Association
الموضوعActive noise control
Ventilation noise
العنوانActive control of noise in ventilation ducts
النوعConference Paper
dc.accessType Abstract Only


الملفات في هذه التسجيلة

الملفاتالحجمالصيغةالعرض

لا توجد ملفات لها صلة بهذه التسجيلة.

هذه التسجيلة تظهر في المجموعات التالية

عرض بسيط للتسجيلة