    JavaScript is disabled for your browser. Some features of this site may not work without it.

    An experimental study on achieving even-frosting for an air source heat pump using a novel dual-fan outdoor coil

    Thumbnail
    View/Open
    Publisher version (You have accessOpen AccessIcon)
    Publisher version (Check access options)
    Check access options
    Date
    2022-01-15
    Author
    Bai, Xiaoxia
    Liu, Shengnan
    Deng, Shiming
    Zhang, Long
    Wei, Minchen
    Metadata
    Show full item record
    Abstract
    Many related studies suggested that a fixed airflow direction usually led to that the most frost would only deposit on the windward side of finned tube heat exchangers (FTHXs) of the traditional single fan outdoor coils in air source heat pumps (ASHPs), result in more frequent defrosting operations and a lower operating efficiency of ASHPs. In this experimental study, to achieve evener frosting on outdoor coils, a novel outdoor coil having two identical fans was proposed. The two fans, Fan A and Fan B, may operate alternately to reverse airflow direction based on a pre-set value of time interval for alternate operation (tTIAO). Feasibility and stability of the novel dual-fan outdoor coil to achieve even frosting on both windward and leeward sides of the FTHX were experimentally studied via seven experimental cases including both single and multiple frosting-defrosting operation cycles. The experimental results demonstrated that when using the novel dual-fan outdoor coil in Cases 3, 4 and 7, the heating/frosting duration was lengthened by 23.6%, 34.5% and 46.4%, and the averaged output heating capacity () was increased by 5.5%, 9.5% and 9.6 %, and averaged COP () by 6.7%, 10.5% and 11.1% respectively, and the defrosting frequency was decreased by 33.3% in Case 7,when compared to using the traditional single-fan outdoor coil. Besides, as tTIAO values were decreased from 15 mins to 10 mins for both fans, and to 6 mins for Fan A and 8 mins for Fan B, heating/frosting operation duration was increased by 8.9% and 19.4%, respectively, at a higher and , as compared to those using the traditional single-fan outdoor coil. The experimental results clearly demonstrated that the use of the novel dual-fan outdoor coil can help achieve evener frosting on both sides of the FTHX, and hence a longer heating operation duration and a higher operating efficiency and output heating capacity.
    DOI/handle
    http://dx.doi.org/10.1016/j.enbuild.2021.111695
    http://hdl.handle.net/10576/33544
    Collections
    • Mechanical & Industrial Engineering [‎1460‎ items ]

    entitlement


    Qatar University Digital Hub is a digital collection operated and maintained by the Qatar University Library and supported by the ITS department

    Contact Us | Send Feedback
    Contact Us | Send Feedback | QU

     

     

    Home

    Submit your QU affiliated work

    Browse

    All of Digital Hub
      Communities & Collections Publication Date Author Title Subject Type Language Publisher
    This Collection
      Publication Date Author Title Subject Type Language Publisher

    My Account

    Login

    Statistics

    View Usage Statistics

    About QSpace

    Vision & Mission

    Help

    Item Submission Publisher policiesUser guides FAQs

    Qatar University Digital Hub is a digital collection operated and maintained by the Qatar University Library and supported by the ITS department

    Contact Us | Send Feedback
    Contact Us | Send Feedback | QU

     

     

    Video