AbstractIndustrial overcurrent relays such as MiCOM P123 (overcurrent and earth fault protection relay) often offer three individual options for separate settings. These settings can be separately tuned and such ability can be utilized to apply the relay as backup of itself. In this system, not only the other relays operate as backup of the current relay, but also settings of the relay operate as backup for themselves. In order to verifying such ability, this paper tunes the settings of MiCOM P123 overcurrent relay as backup of each other to make the non-standard characteristic for overcurrent relay. In the developed model, the first setting of the relay is set on normal inverse (NI) curve, the second setting on very inverse (VI) curve, and the third setting on the instantaneous definite minimum tome (DMT) type. The operating area of the relay is divided into two areas. In the first area, the VI curve operates as backup of NI and in the second area, the NI curve operates as backup of VI. The third setting also operates as backup of both the first and second settings. The system is implemented in the protection laboratory as well as it is simulated using MATLAB software. The simulation outputs are verified and confirmed by the experimental tests. The results confirm that the proposed model has two advantages. The first achievement is to reduce the tripping time by about 5%. And he second advantage is to increase the protection level when one of the settings fails to operate. - 2019 Elsevier B.V.
SponsorThis work was supported by the National Priorities Research Program under grant 11S-1125-170027 from the Qatar National Research Fund (a member of Qatar Foundation).
Languageen
PublisherElsevier B.V.
SubjectBackup operation
Experimental study
Minimum operating time
Non-standard characteristic
Overcurrent relay setting
TitleNon-standard characteristic of overcurrent relay for minimum operating time and maximum protection level