Show simple item record

AuthorGhorbani, Amir
AuthorMehrjerdi, Hasan
Available date2020-06-02T08:17:30Z
Publication Date2019
Publication NameIEEE Transactions on Power Delivery
ResourceScopus
ISSN8858977
URIhttp://dx.doi.org/10.1109/TPWRD.2019.2906056
URIhttp://hdl.handle.net/10576/14995
AbstractThe fault resistance and infeeded currents from tapped transmission lines are the two main challenges to establish correct fault location estimation in multi-terminal transmission lines. Also, fault location estimation in double-circuit lines is more complicated than single-circuit lines due to the effect of mutual coupling and inter-circuit faults. This paper proposes a negative-sequence network-based method to estimate the fault location of double-circuit multi-terminal transmission lines. In the presented method, signals are measured in the relay location and then, communication links are not required as it uses only one end measurements. Also, in conventional distance relays, six elements are needed to calculate the fault location in all types of faults. Furthermore, in this method, by using only one element for each transmission line, accurate fault location can be estimated. Also, high fault resistance, mutual coupling, and infeeded currents from tapped transmission lines do not have impact on the performance of the presented scheme. To investigate the effects of the line shunt capacitances on the proposed method, a PI model of the transmission lines is used in all the investigations. Simulation results carried out using MATLAB software indicate that the proposed scheme is able to produce excellent performance for the fault location estimation. - 2018 IEEE.
SponsorManuscript received August 30, 2018; revised November 30, 2018 and February 24, 2019; accepted March 9, 2019. Date of publication March 18, 2019; date of current version May 22, 2019. This work was supported by the National Priorities Research Program under Grant 11S-1125-170027 from the Qatar National Research Fund (a member of Qatar Foundation). Paper no. TPWRD-00960-2018. (Corresponding author: Amir Ghorbani.) A. Ghorbani is with the Department of Electrical Engineering, Islamic Azad University, Abhar 4561934367, Iran (e-mail:,ghorbani.a@abhariau.ac.ir).
Languageen
PublisherInstitute of Electrical and Electronics Engineers Inc.
Subjectdouble-circuit multi-terminal transmission lines
Fault location
fault resistance
negative-sequence network
TitleNegative-Sequence Network Based Fault Location Scheme for Double-Circuit Multi-Terminal Transmission Lines
TypeArticle
Pagination1109-1117
Issue Number3
Volume Number34