High-speed auxiliary fault location element for distance relays in double-circuit lines
المؤلف | Mehrjerdi, Hasan |
المؤلف | Ghorbani, Amir |
تاريخ الإتاحة | 2022-11-14T10:49:10Z |
تاريخ النشر | 2021 |
اسم المنشور | Electric Power Systems Research |
المصدر | Scopus |
المصدر | 2-s2.0-85111995872 |
الملخص | In multi-zone distance relays, zone-2 has an intentional time delay which is considered for the coordination among the other distance relays. This delay is unnecessary for faults that occur at the end of the protected line and causes the fault to be cleared after hundreds of milliseconds. On the other hand, high-speed fault clearance is an important issue of ensuring the stability of the power system. To address the above problem, an auxiliary fault location (AFL) element based on the proper Kirchhoff voltage law (KVL) loop in the negative- and zero-sequence circuits are designed for distance relays. The input signals to the AFL are the measured signals by local distance relay. The proposed AFL can reduce the zone-2 intentional time delay from 18-28 cycles to 3 cycles. In addition to this, AFL can improve limitations associated with similar methods such as the dependence of these methods to the fault resistance, remote source impedances, and line parameters variation. The AFL can accurately calculate the fault location, before issuing a trip command. Furthermore, to increase the accuracy, the shunt capacitances of the line are compensated by the algorithm. Numerous PSCAD simulation studies verify the effectiveness and applicability of the proposed scheme. 2021 Elsevier B.V. |
راعي المشروع | This work was supported by the National Priorities Research Program under Grant 11S-1125-170027 from the Qatar National Research Fund (a member of Qatar Foundation). |
اللغة | en |
الناشر | Elsevier |
الموضوع | Distance relay Double-circuit transmission lines Fault location Fault resistance |
النوع | Article |
رقم المجلد | 200 |
تحقق من خيارات الوصول
الملفات في هذه التسجيلة
الملفات | الحجم | الصيغة | العرض |
---|---|---|---|
لا توجد ملفات لها صلة بهذه التسجيلة. |
هذه التسجيلة تظهر في المجموعات التالية
-
الهندسة الكهربائية [2649 items ]