Show simple item record

AuthorSoliman, S.A.
AuthorAlammari, R.A.
AuthorEl-Hawary, M.E.
Available date2024-05-23T05:12:38Z
Publication Date2001
Publication NameLESCOPE 2001 - 2001 Large Engineering Systems Conference on Power Engineering: Powering Beyond 2001, Conference Proceedings
ResourceScopus
Identifierhttp://dx.doi.org/10.1109/LESCPE.2001.941637
URIhttp://hdl.handle.net/10576/55330
AbstractThis paper presents a new and very accurate algorithm for power system frequency measurement. The proposed algorithm is based on αβ-transformation of the three phase voltages or current waveforms in the relay location, where digital samples are available for the three phase waveforms. Having obtained the digital samples of one of the components, α-β components, the finite divided difference formulae are used to calculate the parameters of one of these components; the magnitude, the frequency and phase angle. The necessary formulae are derived within the text and effects of imbalance and harmonics contamination on the waveforms are discussed within the text.
Languageen
PublisherInstitute of Electrical and Electronics Engineers Inc.
SubjectEngineering
Industrial engineering
Divided difference
Frequency relaying
Phase angles
Power system frequencies
Relay location
Three phase
Three phase voltage
Wave forms
Algorithms
TitleOn the application of αβ-transformation for power systems frequency relaying
TypeConference Paper
Pagination120-124
dc.accessType Abstract Only


Files in this item

FilesSizeFormatView

There are no files associated with this item.

This item appears in the following Collection(s)

Show simple item record