Show simple item record

AuthorAzani, H.
AuthorMassoud, A.
AuthorBenbrahim, L.
AuthorWilliams, B.W.
AuthorHoliday, D.
Available date2016-05-26T12:20:49Z
Publication Date2014
Publication Name7th IET International Conference on Power Electronics, Machines and Drives, PEMD 2014
ResourceScopus
CitationAzani, H., Massoud, A., Benbrahim, L., Williams, B.W., Holiday, D. "An LCL filter-based grid-interfaced three-phase voltage source inverter: Performance evaluation and stability anaylsis" (2014) 7th IET International Conference on Power Electronics, Machines and Drives, PEMD 2014, .
ISBN978-1-8491-9815-8
URIhttp://dx.doi.org/10.1049/cp.2014.0505
URIhttp://hdl.handle.net/10576/4586
AbstractPower converters in grid connection applications commonly employ Sinusoidal Pulse-Width Modulation (SPWM) technique. Passive filters are employed in order to attenuate the generated switching current ripples and reduces resonances between the grid and the inverter. The first-order (L), the second-order (LC), and the third-order (LCL) filters topologies are typical filters for grid connected Voltage Source Inverters (VSI). Practically, due to the system size, weight, and cost requirements, the LCL filter is the most commonly used among others for the integration of the three phase VSI into the grid. However, the control system stability is affected by the underdamping characteristic of the LCL filter therefore, it introduces to challenges to the control problem. Numerous control strategies such as repetitive, predictive, multiloop control, and hysteresis regulation have been proposed in order to improve the stability of the grid-connected VSIs. In this paper, the performance of the third order LCL filter-based gridconnected three-phase VSI is evaluated and the system stability is investigated using a two-loop control approach with both passive and active damping. The two-loop control considers the grid current as the outer loop while for the inner loop, different variables are considered such as capacitor voltage, capacitor current, and inductor current.
SponsorNPRP grant 4-250-2-080 from the Qatar National Research Fund (a member of Qatar Foundation).
Languageen
PublisherInstitution of Engineering and Technology
SubjectControl system stability
Inverter-based distributed generation
LCL filter
Passive and active filters
circuit stability
electric current control
TitleAn LCL filter-based grid-interfaced three-phase voltage source inverter: Performance evaluation and stability anaylsis